Technical Parameter:
S/N |
Name |
Unit |
Data |
||||
Products Type |
FWX-12 |
FWX-24 |
FWX-40.5 |
||||
1 |
Rated Voltage |
kV |
12 |
24 |
40.5 |
||
6/10/11 |
15/17.5/20 |
33/36/38 |
|||||
2 |
Rated Frequency |
Hz |
50/60 |
50/60 |
50/60 |
||
3 |
Rated Insulation level |
Lightning impulse withstand voltage |
Phase to Phase, Phase to Earth |
kV |
75 |
125 |
185 |
(Fill SF6 gas 0.07Mpa/20℃) |
Fracture |
85 |
145 |
215 |
|||
Power frequency withstand voltage |
Phase to Phase, Phase to Earth |
kV |
42 |
64 |
95 |
||
Fracture |
50 |
79 |
110 |
||||
4 |
Insulation level under zero gauge |
Power frequency withstand voltage |
kV |
30 |
|||
Inverted withstand voltage 1min |
30 |
||||||
Maximum phase voltage 5min |
9 |
||||||
5 |
Rated currency |
A |
630(400) |
630(400) |
630(400) |
||
6 |
Rated breaking load current(0.07Mpa /20℃) |
A |
630(400) |
630(400) |
630(400) |
||
7 |
Breaking current under zero gauge pressure |
A |
630(400) |
630(400) |
630(400) |
||
8 |
Peak withstand current |
kA |
50 |
31.5 |
31.5 |
||
9 |
Rated short-time closing current |
kA |
50 |
31.5 |
31.5 |
http://www.tyouelectric.com/